+2
-0.67

In the system shown below, the generator was initially supplying power to the grid. A temporary LLLG bolted fault occurs at F very close to circuit breaker-1. The circuit breakers open to isolate the line. The fault self-clears. The circuit breakers reclose and restore the line. Which one of the following diagrams best indicates the rotor accelerating and decelerating areas?

GATE EE 2025 Power System Analysis - Power System Stability Question 1 English
A
Fig. (i) GATE EE 2025 Power System Analysis - Power System Stability Question 1 English Option 1
B

Fig. (ii)

GATE EE 2025 Power System Analysis - Power System Stability Question 1 English Option 2
C
Fig. (iii) GATE EE 2025 Power System Analysis - Power System Stability Question 1 English Option 3
D
Fig. (iv) GATE EE 2025 Power System Analysis - Power System Stability Question 1 English Option 4
2
GATE EE 2024
Numerical
+2
-0

The single line diagram of a lossless system is shown in the figure. The system is operating in steady-state at a stable equilibrium point with the power output of the generator being $P_{max} \sin \delta$, where $\delta$ is the load angle and the mechanical power input is $0.5 P_{max}$. A fault occurs on line 2 such that the power output of the generator is less than $0.5 P_{max}$ during the fault. After the fault is cleared by opening line 2, the power output of the generator is $\left\{\frac{P_{max}}{\sqrt{2}} \right\} \sin \delta$. If the critical fault clearing angle is $\frac{\pi}{2}$ radians, the accelerating area on the power angle curve is ______ times $P_{max}$ (rounded off to 2 decimal places).

GATE EE 2024 Power System Analysis - Power System Stability Question 2 English
Your input ____
3
GATE EE 2022
Numerical
+2
-0

Two generating units rated for 250 MW and 400 MW have governor speed regulations of 6% and 6.4%, respectively, from no load to full load. Both the generating units are operating in parallel to share a load of 500 MW. Assuming free governor action, the load shared in MW, by the 250 MW generating unit is ________. (round off to nearest integer).

Your input ____
4
GATE EE 2022
Numerical
+2
-0

A 20 MVA, 11.2 kV, 4-pole, 50 Hz alternator has an inertia constant of 15 MJ/MVA. If the input and output powers of the alternator are 15 MW and 10 MW, respectively, the angular acceleration in mechanical degree/s2 is _________. (round off to nearest integer).

Your input ____